Language
English English Vietnamese (Tiếng Việt) Vietnamese (Tiếng Việt) Chinese (简体中文) Chinese (简体中文) Portuguese (Brazil) (Português do Brasil) Portuguese (Brazil) (Português do Brasil) Spanish (Español) Spanish (Español) Indonesian (Bahasa Indonesia) Indonesian (Bahasa Indonesia)
Tons of Refrigeration to Kilowatts

Tons of Refrigeration to Kilowatts

Turns chiller and CRAH tonnage into kilowatts of cooling, with the IT load each nominal size carries once in-room losses are allowed for.

Matching Chiller and CRAH Tonnage to a Data Hall's kW of IT Load

A data centre keeps two sets of books. The white space is measured in kilowatts — that is how the design load, the UPS blocks, the metered draw and the capacity report are all written. The cooling equipment that has to remove that heat arrives from the vendor labelled in tons: a 30-ton CRAH, a 200-ton chiller, a 500-ton plant. Reconciling the two is a daily job for anyone commissioning a hall or checking whether a new deployment still fits under the plant.

Conversion factor: 1 TR = 3.5168528 kW, so multiply tonnage by roughly 3.517. A 30 TR CRAH is 105.51 kW of cooling; allow about 10 % for fan work, distribution losses and lighting inside the room and it carries around 96 kW of IT load.

Why Both Units Live on the Same Drawing

Plant catalogues still count in tons

Air-cooled scroll chillers, water-cooled centrifugals and packaged room units carry nominal tonnage in the model number, a habit inherited from North American HVAC supply chains.

White space is contracted in kilowatts

Colocation agreements, capacity dashboards and the design load all speak kW. Nobody sells a customer a quarter of a ton of cooling — they sell a committed kW of IT.

Room heat is more than the servers

Fan motors, in-room distribution units and transformers, lighting and the occasional engineer all dump heat into the same volume, so the cooling figure has to sit above the IT figure.

Nominal tonnage is a label, not a promise

The tonnage on the badge is a catalogue size. What a machine actually delivers depends on entering water and air temperatures, so the selection-software output is the number that binds.

Reading a Cooling Schedule Against the Facility Capacity Report

The sequence below is what a facility engineer runs when a vendor quotation lands, or when an operations question — can this hall take another hundred kilowatts? — needs an answer before the change board meets.

1

Type the nameplate tonnage in

Put the unit's ton figure in the left field — 20, 30, 100, 500 — and the kilowatt equivalent appears as you go. Half sizes are common on room units, and a decimal comma works as well as a dot.

2

Take the in-room losses off the top

The kilowatt figure is total heat removal, not IT capacity. Knock off the fan, distribution and lighting share before comparing it with a committed load; on most halls a 10 % allowance is a sensible first pass.

3

Reverse it when the hall load is the known figure

With a 640 kW design load already fixed and the chiller order still open, press the swap button (↔) to run kW → TR. Dividing by 3.5168528 gives about 182 TR of duty before any redundancy is added on top.

4

Lift the clean number into the capacity sheet

The copy button hands over the plain figure with no unit attached, which is what a spreadsheet cell or a capacity-tracking field expects. Ctrl + C inside a field does the same thing.

Rated at what conditions: a chiller's tonnage is quoted at a standard chilled-water temperature and ambient. Raise the supply temperature for efficiency and capacity moves; push the condenser into a 40 °C afternoon and it moves the other way. Convert the selection figure, not the badge.

Cooling Unit Tonnage and the IT Load It Can Carry

Nominal equipment sizes as they appear on quotations, converted to kilowatts of cooling, with the IT load each supports once about 10 % of the hall's heat is set aside for fan work, in-room distribution losses and lighting.

Nominal size Cooling (kW) IT load carried Where it turns up
5 TR 17.58 kW ≈ 16 kW Comms room or a single edge cabinet enclosure
10 TR 35.17 kW ≈ 32 kW Branch server room on a dedicated split system
20 TR 70.34 kW ≈ 64 kW In-row units serving one contained aisle segment
30 TR 105.51 kW ≈ 96 kW A single perimeter CRAH in a modest hall
50 TR 175.84 kW ≈ 160 kW Large downflow room unit or a small modular chiller
100 TR 351.69 kW ≈ 320 kW Air-cooled chiller module in an N+1 bank
200 TR 703.37 kW ≈ 639 kW Water-cooled machine on a small central plant
500 TR 1 758.43 kW ≈ 1 599 kW Centrifugal chiller feeding a 1.5 MW hall

Read down the middle column and the arithmetic that trips people up becomes obvious: a "100 ton" chiller is not a 100 kW machine, it is a 352 kW machine, and three of them running in an N+1 bank protect roughly 640 kW of IT rather than 960 kW. These are also cooling kilowatts, not electrical ones — at a PUE of 1.4 a 320 kW IT load pulls about 448 kW from the meter, but only the white-space share is what the plant has to lift.

What the Converter Gives You During a Capacity Review

Tonnage and kW track each other as you type

Walk an equipment schedule from the smallest in-row unit up to the central plant without clearing the box between entries — the other side follows every keystroke.

Flip to size plant from a committed load

The swap control turns the page into kW → TR, the direction you need when the hall's design kilowatts are fixed and the chiller order is not.

Reach for megawatts when the campus total is the question

Searchable dropdowns on both sides carry every power unit, so the same page steps a plant figure up to MW or across to BTU/h without leaving the tab.

Figures that paste straight into the capacity model

Results run to eight decimals where they matter and copy as a bare number, so nothing needs cleaning up before it lands in a spreadsheet.

Data Hall Cooling Questions

Should I size against a CRAH's total capacity or its sensible capacity?

Sensible, every time. A data hall has almost no moisture to remove — it is a tightly sealed space with tiny outside-air rates and no wet load — so the latent portion of a catalogue's total capacity is capacity you will never use. Room units built for IT duty run at a sensible heat ratio close to 1.0 for exactly this reason. If a schedule quotes a comfort-cooling total figure, take the sensible column before converting to kilowatts, or the hall gets over-promised by a noticeable margin.

How much of the electricity a rack consumes actually comes back as heat?

Effectively all of it. A server does no mechanical work on the outside world; the energy leaves as a trickle of light down a fibre, a little acoustic noise from the fans, and heat. Treating IT watts as watts of heat one for one is standard practice and is accurate to well inside the tolerance of any load estimate. The extra heat you must allow for comes from everything else in the room, not from a shortfall in that assumption.

Chilled water or direct expansion for a new hall?

DX room units keep the refrigerant circuit inside each machine, which makes small and phased builds simple: you buy tonnage as the load arrives and one failure stays contained. Chilled water centralises the refrigeration in a plant room, moves heat around in pipes rather than refrigerant lines, scales far better past a few hundred tons and opens the door to economiser operation. Below roughly a hundred tons the DX route usually wins on cost and simplicity; above it, water tends to take over.

How do I count tonnage once N+1 redundancy is applied?

Only the units left standing after the worst single failure count towards capacity. Four 100 TR chillers in an N+1 arrangement give 300 TR of usable duty — 1 055 kW, not 1 407 kW — and the fourth machine exists to cover a fault or a maintenance window. The same logic applies to room units: if a hall needs six CRAHs to hold temperature, seven get installed, and the capacity report is written against six.

Do free-cooling hours change the tonnage I have to install?

No — they change what the plant costs to run, not what you install. The equipment still has to hold the full load on the hottest afternoon of the design year, so peak conditions set the tonnage. What economisers change is the energy story: in a cool climate, a raised chilled-water temperature can let them carry a large share of the year's hours with the compressors idle or unloaded. Size for the peak, budget the energy on the hours.

TR
kW

Chiller and CRAH Sizes in Kilowatts

5 TR=17.58 kW
10 TR=35.17 kW
20 TR=70.34 kW
30 TR=105.51 kW
100 TR=351.69 kW
500 TR=1 758.43 kW

Ton of Refrigeration (TR)

The nominal size stamped on chillers and room units: 3.5168528 kW of heat removal. It is why a 100-ton machine and a 100 kW hall are nowhere near each other — that chiller is worth 352 kW of cooling.

Kilowatt (kW)

The unit a data centre runs its life in — design load, UPS blocks, committed colocation capacity, metered draw. Converting tonnage into kW puts the cooling plant on the same page as the capacity report.

Enter the nameplate tonnage and read the cooling kilowatts as you type — half sizes and decimals are fine
Press the swap button (↔) for kW → TR when the hall's design load is the figure already fixed
The copy button hands over the bare number, ready to drop into a capacity spreadsheet cell
Switch either dropdown to MW for campus-scale plant totals — the arithmetic never leaves your browser
Want to learn more? Read documentation →
1/5

Power Converter

BTU per Hour to BTU per Minute BTU per Hour to Horsepower BTU per Hour to Kilowatts BTU per Hour to Tons of Refrigeration BTU per Hour to Watts BTU per Minute to BTU per Hour Boiler Horsepower to Horsepower Boiler Horsepower to Kilowatts Calories per Second to Watts Electric Horsepower to Horsepower Electric Horsepower to Kilowatts Foot-pounds per Second to Horsepower Foot-pounds per Second to Watts Gigawatts to Kilowatts Gigawatts to Megawatts Horsepower to BTU per Hour Horsepower to Boiler Horsepower Horsepower to Electric Horsepower Horsepower to Foot-pounds per Second Horsepower to Kilowatts Horsepower to Metric Horsepower Horsepower to Tons of Refrigeration Horsepower to Watts Kilocalories per Hour to Kilowatts Kilocalories per Hour to Watts Kilowatts to BTU per Hour Kilowatts to Boiler Horsepower Kilowatts to Electric Horsepower Kilowatts to Gigawatts Kilowatts to Horsepower Kilowatts to Kilocalories per Hour Kilowatts to Megawatts Kilowatts to Metric Horsepower Kilowatts to Tons of Refrigeration Kilowatts to Watts Megawatts to Gigawatts Megawatts to Kilowatts Megawatts to Watts Metric Horsepower to Horsepower Metric Horsepower to Kilowatts Metric Horsepower to Watts Microwatts to Watts Milliwatts to Watts Tons of Refrigeration to BTU per Hour Tons of Refrigeration to Horsepower Tons of Refrigeration to Kilowatts (current page) Tons of Refrigeration to Watts Watts to BTU per Hour Watts to Calories per Second Watts to Foot-pounds per Second Watts to Horsepower Watts to Kilocalories per Hour Watts to Kilowatts Watts to Megawatts Watts to Metric Horsepower Watts to Microwatts Watts to Milliwatts Watts to Tons of Refrigeration
Start typing to search...
Searching...
No results found
Try searching with different keywords