Appliance Gas Pressures: kPa on One Data Plate, mbar on the Next
A gas fitter carries one manometer and meets two unit systems. Installation standards and appliance labels in Australia and New Zealand quote working pressure in kilopascals — 1.13 kPa at the meter for natural gas, 2.75 kPa for LPG. The same class of appliance sold in the UK and continental Europe states its inlet pressure in millibars, and imported burner instructions, regulator stampings and combustion-analyser printouts follow suit. Reading a test point means being fluent in both.
Where These Small Numbers Come From
The regulator sets the level
Only millibars above the room
Working versus standing
Gas type changes everything
Checking a Test-Point Reading in Both Units
The sequence below assumes the manometer is already on the inlet or burner test point and the appliance is at rate.
Enter what the gauge says
If the instrument reads kilopascals, type it on the left — 1.13, 2.75, 0.87 — and millibars appear alongside. Decimal commas are accepted and stray spaces are ignored, which helps when a figure is copied out of a manual.
Hold it against the rating plate
Compare the converted value with the nominal pressure the manufacturer prints for that gas. A burner asking 37 mbar and a supply delivering 2.8 kPa are not the same thing — that is 28 mbar, a butane level on a propane appliance.
Move the figure to the paperwork
The copy button on either field puts the number on the clipboard with no unit attached, which is what a commissioning record or a certificate field expects. Pressing Ctrl + C in the field has the same effect.
Turn it round for the European spec
Press the swap arrows (↔) and the page runs mbar → kPa instead, for the far more common case of a British or European document quoting millibars to someone working in kilopascals. That direction is simply a division by ten: 37 mbar is 3.7 kPa.
Supply and Burner Pressures by Gas Type
Nominal figures that appear on rating plates, regulators and test-point specifications, written in both units. Actual acceptable ranges come from the appliance instructions and the local installation standard — these are the reference points those documents are built around.
| Gas and context | kPa | mbar | Where it is quoted |
|---|---|---|---|
| Natural gas, appliance inlet | 2.0 kPa | 20 mbar | UK and much of continental Europe |
| Natural gas, metering pressure | 1.13 kPa | 11.3 mbar | Australian standard domestic installation |
| Natural gas, appliance operating | 1.1 kPa | 11 mbar | Australia and New Zealand |
| Butane, cylinder regulator | 2.8 kPa | 28 mbar | UK low-pressure butane fittings |
| Butane/propane combination regulator | 3.0 kPa | 30 mbar | Common European leisure and catering kit |
| Propane, low-pressure regulator | 3.7 kPa | 37 mbar | UK and European propane appliances |
| LPG, appliance supply | 2.75 kPa | 27.5 mbar | Australia and New Zealand |
| Natural gas burner, 3.5 in water column | 0.87 kPa | 8.7 mbar | North American manifold pressure |
| Propane burner, 11 in water column | 2.74 kPa | 27.4 mbar | North American manifold pressure |
Two patterns stand out. LPG always sits above natural gas, because it carries far more energy per cubic metre and the appliance compensates with much smaller injectors. And every figure in the table fits inside four kilopascals — under four per cent of atmospheric pressure — which is why gas manometers are built with a narrow span and read in tenths.
What This Page Does on a Service Call
Both fields follow the gauge
Type into whichever box matches your instrument and the other keeps pace, so a working-pressure and a standing-pressure reading can be checked one after the other.
One press to read the import manual
The swap arrows reverse the pair for millibar-to-kilopascal work, which is the direction most imported appliance literature forces on you.
Water column is in the list too
Both unit menus are searchable and cover mmH₂O and inH₂O alongside all the other pressure units, so a U-tube figure or a North American manifold spec converts on the same screen.
Certificate-ready digits
Copy hands over the number by itself, and results carry up to eight decimals, so a reading like 1.13 kPa lands as 11.3 rather than something you have to retype.
Gas Pressure Questions From the Test Point
Why does the same appliance quote millibars in Europe and kilopascals in Australia?
Both units measure exactly the same thing and differ only by a factor of ten. The European gas trade inherited the millibar from meteorology and kept it because appliance pressures land on convenient whole numbers — 20, 28, 30, 37. Australian and New Zealand standards went with the SI-derived kilopascal instead, so the same pressures appear as 2.0, 2.8, 3.0 and 3.7.
What is the difference between inlet working pressure and burner pressure?
Inlet working pressure is measured at the appliance connection with the burner alight, and it tells you what the supply and pipework can deliver under load. Burner or manifold pressure is measured downstream of the appliance gas valve and tells you what the injectors actually see. A healthy inlet figure with a low burner figure points at the valve or its adjustment rather than the supply.
What does regulator lock-up pressure tell a fitter?
Lock-up is the standing pressure the regulator settles at once every appliance is off. It always sits a little above working pressure, and the manufacturer states how much. A lock-up that climbs well past the stated allowance means the regulator is not sealing, which can push the appliance above its rated inlet pressure — the sort of drift that only shows up when you compare the firing and shut-off readings.
Why do appliances run on only a few tens of millibars?
An atmospheric burner does not need pressure, it needs flow and the right air entrainment. A gentle push of two or three kilopascals through a correctly sized injector gives the gas rate and jet velocity the venturi is designed around. Raising the pressure would lift the flame off the ports and upset combustion long before it improved anything.
How do inches of water column relate to these millibar and kilopascal figures?
One inch of water column is 249.09 Pa, so it is very close to 2.5 mbar or 0.25 kPa. That makes the North American 3.5 in WC natural-gas manifold figure about 8.7 mbar, and the 11 in WC propane figure about 27.4 mbar. Pick inH₂O or mmH₂O in either dropdown and the page handles that step for you.
No comments yet. Be the first to comment!