Language
English English Vietnamese (Tiếng Việt) Vietnamese (Tiếng Việt) Chinese (简体中文) Chinese (简体中文) Portuguese (Brazil) (Português do Brasil) Portuguese (Brazil) (Português do Brasil) Spanish (Español) Spanish (Español) Indonesian (Bahasa Indonesia) Indonesian (Bahasa Indonesia)

Bridges the bar used for piped medical gas with the mmHg printed on suction regulators, with a table of hospital gas and vacuum service levels.

One Hospital, Two Pressure Scales on the Same Wall

Walk a ward with a biomedical engineer and you cross a unit boundary every few metres. The piped services behind the head wall — oxygen, medical air, nitrous oxide — are designed, tested and labelled in bar. Plug a suction regulator into the vacuum terminal a hand's width away and its dial is graduated in millimetres of mercury. Same plant room, same commissioning visit, two scales, and any figure that moves between the pipework file and the device paperwork has to be converted on the way.

Factor: 1 bar = 750.061683 mmHg. A pipeline running at a nominal 4 bar is 3000.25 mmHg, and a vacuum terminal pulling 300 mmHg below atmosphere is 0.4 bar of differential.

The Services Behind the Head Wall

Positive-pressure services

Oxygen, medical air and nitrous oxide are distributed at a nominal 4 bar, with a separate 7 bar air service reserved for driving surgical tools. Line regulators and area valve service units hold those levels across the building.

The vacuum side

Medical vacuum is a service in its own right: pumps, receivers, bacterial filters and a pipeline sized so that a busy theatre suite still meets the required vacuum with several inlets flowing at once.

Terminal units and regulators

Gas-specific probes stop the wrong device reaching the wrong service. Downstream of them, regulators and flowmeters translate a pipeline figure into whatever a device needs — and their scales rarely match the pipeline's.

Cylinders as backup

A full oxygen cylinder holds far more pressure than any pipeline: around 137 bar at 15 °C, which the regulator knocks down to the 4 bar the equipment expects.

Checking a Terminal Unit Against Its Specification

Whether you are witnessing a commissioning test, closing a planned maintenance job or investigating a report of weak suction, the figures come off two instruments with different scales.

1

Enter the pipeline figure in bar

Type what the test gauge on the terminal-unit probe shows — 4, 4.2, 6.9. The millimetres of mercury appear straight away, and a comma is accepted instead of a full stop for anyone using a European keypad.

2

Flip the direction for the suction side

Suction figures arrive the other way round. Press the swap arrow (↔) to run mmHg → bar and see what a 400 mmHg regulator setting represents as a differential — 0.533 bar below atmosphere.

3

Copy the number into the asset record

The copy button on each field puts the digits alone on the clipboard, with no unit and no spacing, ready to paste into a CMMS work order or a test certificate. Ctrl + C inside a field does the same.

4

Reach for kPa when the standard asks for it

Several national standards state vacuum in kilopascals and some device labels use inches of mercury. Both dropdowns are searchable and cover all 26 units, so the third scale is one selection away.

Engineering figures, not clinical ones: the values here describe pipework, terminal units and device scales. What a regulator should be set to for a given patient or procedure is decided by clinical protocol, not by a conversion table.

Piped Medical Gas and Vacuum Services Side by Side

Representative design and test levels for the services one estates team looks after. Nominal pipeline pressures follow common design practice; verify against the standard in force locally and the scheme's own commissioning documents before using any figure in anger.

Service Typical level (bar) Same value (mmHg) Where it appears
Oxygen pipeline, nominal 4 bar 3000.25 mmHg Terminal units on wards and theatres
Medical air, respiratory (air 4) 4 bar 3000.25 mmHg Ventilators, blenders, humidifiers
Nitrous oxide and N₂O / O₂ mixture 4 bar 3000.25 mmHg Anaesthetic and delivery-suite outlets
Surgical air (air 7) 7 bar 5250.43 mmHg Bone saws, drills, tourniquet supplies
Oxygen cylinder, full at 15 °C 137 bar 102 758.45 mmHg Backup manifold and transport cylinders
Medical vacuum at a terminal unit 0.4 bar below ambient 300.02 mmHg Pipeline performance and commissioning tests
Suction regulator, lower band 0.16 bar below ambient 120.01 mmHg Device dial, gentle settings
Suction regulator, upper band 0.533 bar below ambient 399.78 mmHg Device dial, near the top of a 0–400 scale

The asymmetry is worth noticing: the pressure services live in a narrow band a few times atmospheric, while the vacuum service can never exceed one atmosphere of differential — about 760 mmHg, or roughly 1.013 bar — no matter how large the pump set is.

What the Page Offers an Estates or Biomed Team

Pipeline side and device side at once

Both boxes accept typing and update each other live, so you can walk a regulator's scale from one end to the other and watch the bar differential follow every step.

Whichever scale the paperwork starts on

The swap arrow reverses the pair, which matters because pipeline documents arrive in bar and device manuals arrive in mmHg.

Every unit a medical gas file contains

Searchable dropdowns list all 26 pressure units across eight groups, covering kPa in a national standard, inHg on an imported device and psi on a manifold gauge.

Test-sheet ready values

Results carry up to eight decimals with thousands spaced apart for legibility, and copying gives the bare figure a certificate field can take unedited.

Medical Gas and Vacuum Pipeline Questions

Does a 4 bar pipeline still read 4 bar when several outlets are flowing?

Not quite, and it is not meant to. The nominal figure is a design pressure at the terminal unit; standards specify a pressure that must be maintained while a stated flow is drawn, because that is the condition a ventilator actually sees. A pipeline that reads 4 bar (3000.25 mmHg) statically but sags badly under simultaneous demand has an undersized run, a partly closed valve or a struggling regulator, which is why flow tests are part of commissioning rather than a static gauge check.

Why are suction regulators graduated in mmHg when the plant is designed in bar?

The device scale follows the clinical literature, and mercury has been the reference for medical measurement since long before pipelines existed. The plant follows engineering practice, where bar and kPa dominate. Neither community has an incentive to change, so the boundary sits at the terminal unit: bar on the wall side, mmHg on the device side, with the engineer converting across it.

What do the low, medium and high positions on a suction regulator correspond to?

They are bands on the device dial rather than fixed numbers, and manufacturers place them differently — commonly around 100 to 125 mmHg for the low band, roughly 200 mmHg in the middle and up towards 400 mmHg at the top, which is about 0.13, 0.27 and 0.53 bar of differential. Full-scale ranges of 0–160, 0–300 and 0–760 mmHg are all sold. Check the individual model's scale during acceptance testing; which band gets used on a patient is a clinical decision.

Do oxygen and medical air run at the same pipeline pressure?

The respiratory services generally do — oxygen, medical air and nitrous oxide are commonly distributed at the same nominal 4 bar so that blenders and ventilators see balanced supplies. Surgical air is the exception: it is a separate 7 bar (about 5250 mmHg) service because pneumatic tools need the extra pressure, and it is piped and terminated separately so it can never be mistaken for the respiratory supply.

What does a vacuum quoted as −400 mmHg actually mean?

It is 400 mmHg below whatever the local atmospheric pressure happens to be — a differential of 0.533 bar, not an absolute pressure. At sea level that leaves roughly 360 mmHg of absolute pressure in the line. The distinction matters at altitude, where atmospheric pressure is lower and the same regulator setting is a larger share of the total available differential, so a site's achievable vacuum should be assessed against its own ambient pressure.

bar
mmHg

Medical Gas and Vacuum Levels

0.16 bar=120.01 mmHg
0.4 bar=300.02 mmHg
0.533 bar=399.78 mmHg
4 bar=3000.25 mmHg
7 bar=5250.43 mmHg
137 bar=102 758.45 mmHg

Bar (bar)

The unit piped medical services are designed, tested and labelled in: a nominal 4 bar for oxygen, medical air and nitrous oxide, 7 bar for the separate surgical air service, and around 137 bar in a full backup cylinder.

Millimetre of mercury (mmHg)

The scale printed on suction regulators and vacuum gauges at the bedside. Because it counts downwards from ambient, a medical vacuum service can never exceed roughly 760 mmHg of differential at sea level.

Enter the pipeline reading in bar to see the millimetres of mercury a device dial would show
Press the swap arrow (↔) to work from a suction regulator setting back to a bar differential
The copy button gives a bare figure that pastes cleanly into a work order or test certificate
Switch either side to kPa or inHg for standards and imported devices — everything is worked out in your browser
Want to learn more? Read documentation →
1/5

Pressure Converter

Atmospheres to Bar Atmospheres to Kilopascals Atmospheres to PSI Atmospheres to Pascals Atmospheres to Torr Atmospheres to mmHg Bar to Atmospheres Bar to Kilopascals Bar to Megapascals Bar to Millibar Bar to PSI Bar to Pascals Bar to kg/cm² Bar to mmHg (current page) Kilopascals to Atmospheres Kilopascals to Bar Kilopascals to Millibar Kilopascals to PSI Kilopascals to Pascals Kilopascals to inHg Kilopascals to mmHg Megapascals to Bar Megapascals to PSI Millibar to Bar Millibar to Kilopascals Millibar to Torr Millibar to inHg PSI to Atmospheres PSI to Bar PSI to Kilopascals PSI to Megapascals PSI to Pascals PSI to inHg PSI to kg/cm² PSI to mmHg Pascals to Atmospheres Pascals to Bar Pascals to Kilopascals Pascals to PSI Torr to Atmospheres Torr to Millibar Torr to mmHg inHg to Kilopascals inHg to Millibar inHg to PSI kg/cm² to Bar kg/cm² to PSI mmHg to Atmospheres mmHg to Bar mmHg to Kilopascals mmHg to PSI mmHg to Torr
Start typing to search...
Searching...
No results found
Try searching with different keywords