Reading a Pressure-Enthalpy Chart in Two Unit Systems
Refrigerant property data is published in SI. Open a P-h chart, a saturation table or a manufacturer's compressor selection file and the enthalpy axis is in kJ/kg, pressures are in bar and mass flow is in kg/s. Then the job in front of you is rated in tons, the customer's paperwork says BTU/h and the recovery cylinder is weighed in pounds. Every refrigeration technician who works from real property data ends up crossing that boundary, and the crossing starts with the kilojoule.
What the Numbers on the Chart Actually Are
Enthalpy Is Per Unit Mass
Refrigeration Effect Is a Difference
Superheat and Subcooling Shift the Endpoints
Mass Units Cross Over Too
Converting a Δh Figure While the Gauges Are Still On
Read the chart, do the subtraction in SI, then convert once. Converting each endpoint separately doubles the rounding for no benefit.
Take both enthalpies off the chart first
Fix the evaporator outlet from suction pressure plus measured superheat, and the expansion-valve inlet from condensing pressure minus subcooling. Subtract the two to get the refrigeration effect in kJ/kg.
Enter that difference on the kJ side
The BTU figure follows each keystroke. A decimal comma is read the same as a decimal point, which matters when the property table you are working from was printed in Europe.
Reverse it for an imperial property table
The swap arrows send BTU back into kilojoules, which is how an older BTU/lb table lines up against an SI compressor file. The searchable lists on both sides also reach J, MJ, Wh and kWh for the electrical side of the same machine.
Carry the bare figure into the capacity sheet
The copy control above each field takes the digits alone, with no unit and no spacing, so the value goes straight into a service report or a capacity spreadsheet. Ctrl+C inside a field behaves the same way.
Refrigerant Latent Heat in kJ/kg and BTU/lb
Latent heat at roughly 0 °C (32 °F) saturation, which is a fair reference for comparing how much heat each kilogram of refrigerant can absorb as it boils. Values are rounded; always work from the property table that matches your actual evaporating temperature.
| Refrigerant | Type | Latent heat (kJ/kg) | Latent heat (BTU/lb) |
|---|---|---|---|
| R-717 (ammonia) | Natural, industrial | 1 262 | 542.6 |
| R-290 (propane) | Hydrocarbon | 374.5 | 161.0 |
| R-32 | Single-component HFC | 315 | 135.4 |
| R-744 (CO2) | Natural, transcritical | 231 | 99.3 |
| R-410A | HFC blend | 221 | 95.0 |
| R-134a | Single-component HFC | 198.6 | 85.4 |
| R-404A | HFC blend | 165 | 70.9 |
Read down the table and the design consequence is obvious: ammonia carries roughly six times the heat per kilogram that R-404A does, so an industrial ammonia plant moves the same duty on a fraction of the charge and with far smaller liquid lines. At the other end, R-404A's low latent heat is one reason its systems circulate so much refrigerant for the capacity they deliver.
What This Helps With on a Service Call
Suction and Discharge Values Side by Side
Both boxes stay live, so a chart reading and its imperial equivalent can be compared without clearing the field and starting again between the two ends of the cycle.
Figures Clean Enough to Paste into a Capacity Sheet
Copied results contain digits only, with no unit label attached, so a converted Δh lands in a service report or a spreadsheet as a number rather than as text.
The Whole Energy List for Property Tables
Searchable dropdowns on both sides cover J, kJ, MJ, Wh, kWh, BTU and more, which covers the mix of units spread across a refrigerant table and the compressor's electrical data.
Small Enthalpy Steps Without Rounding to Zero
Compressor work per kilogram can be a fraction of the refrigeration effect. Results keep up to eight decimals, so a small Δh does not collapse to a round figure before you can use it.
Questions from the Service Van About Enthalpy Units
I have Δh in kJ/kg off the chart — how do I end up with BTU/h of capacity?
Multiply the refrigeration effect by the mass flow. At 0.05 kg/s with a 180 kJ/kg effect the evaporator is absorbing 9 kW. Kilowatts convert to BTU per hour at 3 412.14, so that is about 30 709 BTU/h — a little over two and a half tons. Do the enthalpy subtraction in SI, multiply by flow, and cross to imperial once at the very end.
Why is ammonia's latent heat so much bigger than R-410A's, and what does that change?
Ammonia is a small, strongly hydrogen-bonded molecule with a very low molar mass, so a kilogram of it contains a huge number of molecules and takes an enormous amount of energy to boil — around 1 262 kJ/kg against roughly 221 for R-410A. In practice that means an ammonia plant moves the same duty on a fraction of the refrigerant charge, with smaller pipework and less inventory to leak, which is a large part of why industrial refrigeration stayed with it.
How do I use a European compressor data sheet on a US job?
The sheet will give capacity in kW at stated evaporating and condensing temperatures, with enthalpies in kJ/kg. Convert the capacity to BTU/h by multiplying by 3 412.14, and divide by 12 000 if the job talks in tons. Check the rating conditions before anything else — European selections are commonly published at different evaporating and condensing temperatures than US practice, and that difference will move the capacity more than any unit conversion does.
Why do two tables give different enthalpies for the same refrigerant at the same temperature?
Because enthalpy has no absolute zero — each publisher picks a reference state and counts from there. The IIR convention sets liquid enthalpy to 200 kJ/kg at 0 °C; the older ASHRAE convention uses 0 at −40 degrees. Two tables can therefore differ by a constant on every line and still be equally correct. Differences between two points on the same table are unaffected, which is why every real calculation uses a Δh.
My recovery scale reads pounds but the charge is specified in kilograms — how do I reconcile that?
One kilogram is 2.2046 pounds, so a 3.5 kg factory charge is 7.72 lb. The energy meaning follows from the latent heat: with R-410A at roughly 221 kJ/kg, every kilogram lost is about 221 kJ of cooling per circulation cycle that the system no longer delivers. Converting the same figure to BTU/lb — 95.0 for R-410A — lets you quote the shortfall in the units the customer's paperwork already uses.
No comments yet. Be the first to comment!